10 kV小电阻接地系统的参数特点及其短路计算

申请免费试用、咨询电话:400-8352-114

摘 要:
介绍了10kV小电阻接地系统的特点,采用对称分量法对单相接地故障进行了序网分析,在给定的初始参数条件下,提出了小电阻接地系统参数的一些特点,并作了分析计算,得出单相接地故障时系统线电压仍维持平衡的结论。最后对有关接地设备的选择给出了计算方法。
关键词:中性点小电阻接地;对称分量法;短路计算

Parametric attributes of 10 kV power system grounded by small resistance and its short-circuit calculation
Abstract:The features of 10 kV distribution system grounded by small resistance are described in this paper.The sequential network analysis of single-phase earth fault is conducted using the symmetrical component method.Given initial parameters,some parametric attributes of such system are presented along with analytical computation.It draws a conclusion that the line voltage of the system remains balanced in spite of single-phase ground faults.The computing method for selecting relevant grounding apparatus is proposed at last.
Key words:neutral grounding by small resistance;symmetrical component method;short circuit calculation
  中性点经小电阻接地的配电系统在城市电网中已越来越广泛地被采用。部分城市电网主要以电缆作为送电线路,且使用紧凑型的全封闭式的开关设备及氧化锌避雷器,有些城市使用了不少耐压标准较低的电缆。这样的系统有几个特点:a)系统电容电流较大,通常超过50 A,单相接地故障后会产生较高的内部过电压;b)单相接地故障概率比架空出线少得多;c)设备不允许在单相接地后约3倍的工频过电压下再连续运行。这样要求当系统发生单相接地后应立即切除故障线路,采用小电阻接地有利于继电保护装置可靠迅速地检测并切除故障回路,小电阻接地还可改善系统参数减少接地故障时的内部过电压值。
  小电阻接地系统的分析计算在有关手册及参考书中均未做深入的研究,本文尝试在这方面进行一些分析探讨。
 